Assignment 5 - 2014

From Process Control: 3P4
Jump to navigation Jump to search
The printable version is no longer supported and may have rendering errors. Please update your browser bookmarks and please use the default browser print function instead.
Due date(s): 12 March 2014, in class
Nuvola mimetypes pdf.png (PDF) Assignment questions
Nuvola mimetypes pdf.png (PDF) Assignment solutions

<rst> <rst-options: 'toc' = False/> <rst-options: 'reset-figures' = False/>

.. rubric:: This assignment is due on Wednesday, 12 March 2014. Late hand-ins are not allowed. Since it is posted mainly for you to practice for the midterm, there is no need to submit it. However, if you submit it, we will drop the assignment with the lowest grade to calculate your assignment average. So this is a way to boost your assignment portion of your overall grade.

.. question:: :grading: 5

Many practical chemical engineering systems occur in series, for example heat exchangers, or a sequence of reactors.

.. image:: ../figures/process-control/Marlin-slides/Marlin-series-items.png :scale: 55 :width: 500px

Consider tanks in series, each with a transfer function :math:`G_{p,i}(s)= \dfrac{X_{i+1}(s)}{X_i(s)} =\dfrac{K}{\tau s + 1} = \dfrac{1.5}{4s+1}`.

The :math:`X_i` in this example might, for example, refer to the concentration of product leaving each reactor, in deviation form.

#. Create a Simulink model for 5 such units is series. Supply a step input of 2 units into the first tank. Plot and show the concentration leaving the last tank.

#. What is the gain of the system?

#. Not for grade, but strongly recommended because it is easy practice: use your Simulink model output from the last tank, and fit a first-order plus time delay model, :math:`G_p = \dfrac{K_p e^{-\theta s}}{\tau s + 1}` to the plotted data from part 1.

What values of process gain, :math:`K_p`, process time constant, :math:`\tau`, and process time delay, :math:`\theta`, do you observe? Does the gain match the gain from part 2 of this question? What do notice about the FOPTD time constant, :math:`\tau`?

.. question:: :grading: 10

*From a previous midterm*; this question is also in the next assignment.

In the process below it is desired to control the temperature of the fluid within the tank by manipulating the flow rate :math:`F_A`. The temperature of stream B, :math:`T_B` is expected to fluctuate. :math:`T_A` and :math:`F_B`, and the liquid volume in the tank are assumed constant.

.. image:: ../figures/process-control/CLES/Swartz-midterm.png :scale: 50 :width: 500px

An energy balance on the tank gives: :math:`T'(s) = \dfrac{18}{2s+1}F_A'(s) + \dfrac{0.6}{2s+1}T_B'(s)`

where :math:`F_A` is in L/min, :math:`T` and :math:`T_B` are in Kelvin, and the time constant is in minutes. The true tank temperature is not what is recorded by the sensor. In fact, the measured temperature, :math:`T_m = 0.15T`, where :math:`T_m` is a signal value in milliamps, mA.

It is this measured signal, in mA, that is used to feed back and send to the controller, ``TC``. The controller has to send a signal to the valve to open or close it. It does this by sending a signal, in mA, to the valve. This signal travels at least 1000 m across the plant network to reach the valve, which is why an electrical signal is preferred.

At the valve is an I/P transducer (search the internet for what this term means), which converts the signal to a pressure, in psig. If the I/P transducer receives a 4mA signal, it creates a 3 psig output. If it receives a 20 mA signal, it provides a 20 psig output. This pressure counteracts a spring in the valve to open or close it. The 4mA and 20mA are the lowest and highest signals possible, corresponding to the valve being fully shut and open, respectively. All other valve positions are linearly between these points.

Finally, the pressure output causes the valve to slowly open or close (i.e. it is not instantly opened or closed). When the pressure is suddenly increased by 2mA, we notice that the response in the flow rate, :math:`F_A`, is a first order output, with a final value of 1 L/min higher, taking about 0.5 minutes to completely reach this increased flow.

Use the above information and draw a block diagram of all the systems described here, clearly showing the manipulated variable, disturbance, and show blocks for the temperature sensor, I/P transducer and valve. Show all units on the lines connecting the blocks.

.. question:: :grading: 10

The following diagram is shown in Marlin's textbook, Figure, Q6.4, page 202.

.. image:: ../figures/process-control/Marlin-slides/Marlin-Q6-3-p202.png :scale: 40 :width: 500px

If the the valve position at F2 is opened 5% more (on the left axis), then the corresponding temperature output response at ``T4`` is observed (right axis)

.. image:: ../figures/process-control/Marlin-slides/Marlin-Q6-4-p202.png :scale: 70 :width: 500px

#. Explain why the response in temperature is expected. In your response report whether the reaction in the reactor is exothermic or endothermic.

#. Your goal is to control ``T4`` to be fairly constant, by using the flow rate of ``F2`` (i.e. the valve position just after the ``F2`` flow meter).

List at least 5 plausible disturbances that will cause ``T4`` to deviate from the desired set point.

#. Use the process model computed in the prior part to tune PID controllers settings :math:`K_c, T_I` and :math:`T_D` for a regular PID controller.